Every day to learn a little bit, progress in inadvertently
Southeast network news:
On the afternoon of December 17, 2016, Putian, Xiuyu four new fire with the police, said the town of Xiuyu District, a printing and dyeing factory on the cloth fire. After receiving the alarm, the fire brigade immediately to the scene disposal.
According to the person in charge of the factory, fire is the setting machine is working, the fire broke out in shaping machine is in operation, easy organization factory staff using fire hydrant, fire extinguishers and other tools, the fire extinguishing and control early, and immediately to the police. Fire officers understand the situation, immediately took over the scene, a single route out of three water jets on the cooling stenters around, using plant fire hydrant water cannon on the surrounding temperature. Fire officers and soldiers after a few minutes to ensure without any hidden trouble in the field after finishing equipment rejoin.
Dyeing and finishing machine
Prevention and emergency plan
The setting machine in the flue and memory product oils, cloth wool cloth and a large number of resins in the process of production and processing, daily use temperature is very high, once the fire is difficult to save, not easy to find the beginning of the fire, the flames from the roof of a chimney in the wool cloth entrainment combustion easily ignited other workshop roof. So in the daily work should focus on prevention, fire fighting after not blindly.
One
Routine prevention
1, a day before the shift in the surrounding environment and health, setting machine, set-top set-top machine flue appearance, screen, electric box surrounding cloth hair must be clean.
2, every 15 days for a health, including the machine, remove the screen with air cleaner dry heat exchanger tube net cloth wool, open set-top flue check mouth, clean flue hair cloth.
3, the opening of the exhaust fan to clean the dust inside the fan, oil
Note: must be in the stereotypes of the total power supply has been shut off or exhaust fan power has been closed and to have someone to guard the power switch, to prevent the removal of the exhaust fan when someone mistakenly turn on the power switch.
4, each employee should know how to use dry powder fire extinguisher, each class will have more than four people will use a fire hydrant to open fire pump, fire extinguisher shall not use non use, non destruction, reactor pressure, or stole the fire extinguisher and parts.
5, each employee must clear escape route, daily to ensure safe channel is smooth, fire fighting steam to 15 days to test a.
6, all type boiler heating up to more than 100 degrees, setting machine should start top exhaust fan and oven circulating fan, oil temperature rise in the boiler is not enough when the temperature to zero, not conducive to heating boiler heating.
7, if there is a power outage in the oven door must be opened to cool.
8, down prior to the boiler oil temperature dropped to 100 degrees below can be shut down.
If there is a stop setting machine, to put the temperature table transferred to zero the cabinet door open cooling, electric three check valve is closed after cooling, if the individual failure is not closed well, please close the valve manually, don't let the oil into the oven.
Two
Fire emergency
1, if the setting machine has great roof chimney outlet flue fire smoke, should be immediately reported to the captain, and in charge of shutting down the circulating fan and exhaust fan, the thermostat to cool, don't open the oven door, opened a dedicated fire-fighting steam valve to flue spray steam, group product factory in duty firefighters and participated in the training of the fire personnel arrived at the scene, concentrated fire extinguisher.
2, after the first set of exhaust fan to the roof of the fire in this section, you can open a smoke pipe fire fighting pump, open the corresponding water valve for fire fighting.
3, if the appearance of the insulation cotton flue fire extinguisher can fire with dry powder fire, large area to focus on the multiple fire extinguishers and fire extinguishing ability is effective, if the outdoor appearance of large fire flue available water to extinguish the fire, but not to the local electric spray
(such as: workshop lighting, machine room, toilet lamp, cylinder etc.).
4, if there is smoke can slowly open a door to check, who stood behind the door, because when the door is opened inside the oven fire suddenly to spray, fire can not destroy the box did not shut the door, try not to spray the oven, because the mechanical parts in high temperature and a water jet cooling will affect the normal use of deformation.
If the oven has a lot of black smoke, be sure to check whether the pipeline leakage, such as leakage phenomenon does have two big pipe off the main valve immediately, such as the oil spill more immediately call 119 alarm, evacuation of staff from the scene waiting for the arrangement, leaking out of the box oil fire water can not be directly used to spray, sand don't let the oil containment spread to other places.
Chinatex Jiu (Quanzhou) edited
For more details, please pay attention to the "public", "Fu Tai Printing and dyeing
Attention after the click after entering the top public no."
We can always pay attention to the dynamic
Hotline: 0591-38855525
Long press attention